Alarm range
: 30-400 fpm (.15-2.0 m/s)
Accuracy
: Face velocity accuracy +/- 10%
Airflow sensor
: On-board or remote sensor
Calibration
: Single or 2-point (Installer selectable)
Low Air Alarm delay
: Fixed 5 secs
Relay output
: 1-(Low Air alarm)
Analog output
: Not available
Relay input
: 2-Night setback and sash high
Comm. Port
: RS232 Can be connected via serial interface to LAN network(Full hood performance software reporting available)
Sash high indication
: Yes-using a Micro switch or Proximity switch input With repeat alarm feature factory set to 5 min. (Can be adjusted via laptop up to 30 mins)
Night setback
: Yes-using a relay input
Power Requirement
: Input-120VAC, 60Hz
Output-15VDC, 500ma
External alarm indication
: Not available
Display-visual
: LEDs: red, alarm; green, normal
Alarm indication
: Red LED and audible alarm
Horn silence
: Yes-temporary
Mounting
: Semi Flush
Operating temperature
: 55-86 F (13-30 C)
Storage temperature
: -40-150 F (-40-65 C)
Instrument dimensions
: Instrument Case: 5.2" H x 3.19" W x 1.97" D (132mm H x 81mm W x 50mm D)
Agency listings
: UL and CE
Display range
: 0-999 fpm (0-5.0 m/s)
Alarm range
: 0-999 fpm (0-5.0 m/s)
Field set-up
: 2-point velocity calibration (with on-screen instructions)
Accuracy
: Sensor / Display resolution 1 fpm Face velocity accuracy +/-10%
Alarm delays
: User configurable - 0 to 60secs
Relay output
: 4 (1 on board - 3 on optional plug in relay interface unit)
Analog output
: 0-10V output, directly proportional to velocity (Optional)
Relay input
: 3
Comm. Port
: RS232 Can be connected via Serial interface to LAN network (Full software available)
Sash high indication
: Yes, with separate plug-in connection
Night setback
: Yes
External alarm indication
: Yes
Power Requirement
: Input-120VAC, 60Hz
Output-15VDC, 500ma
Units
: English and Metric (user selectable)
Display-visual
: Analog bar graph or Fault Timeline LEDs: red, alarm; yellow, caution; green, normal Digital display of velocity reading (can be turned off)
Alarm indication
: Red LED and audible alarm (to a certain sound spec)
Horn silence
: Yes (temporary/permanent/automatic depending on type of alarm or external input)
Mounting
: Semi Flush
Operating temperature
: 55-86 F (13-30 C)
Storage temperature
: -40-150 F (-40-65 C)
Instrument dimensions
: Instrument Case: 5.2" H x 3.19" W x 1.14" D (132mm H x 81mm W x 29mm D)
Agency listings
: UL and CE